Knowledge Base › Wiring guide: All-O-Matic SL-90 DC

Wiring guide: All-O-Matic SL-90 DC

This guide shows where each wire from the Nimbio terminal strip lands on the All-O-Matic SL-90 DC’s ALL-BLDC circuit board, and which relay setting Gate Status needs. Gate Status: wired. Sense 1 and SC connect across the board’s RELAY-1 contact, and Nimbio maps the relay’s two states to the labels shown in the app. RELAY-1 is on newer SL-90 boards only (see Gate Status).

Printable version (PDF)

Before you start

  • Power the operator down at its supply before touching any terminal.
  • The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires Sense 1 and SC; Sense 2 is not used (see “Connections”).
  • Power: PWR+ and PWR- land on the board’s +24VDC and GROUND terminals, rated up to 500 mA for accessories. The Nimbio board draws 40 to 70 mA.
  • You need a small screwdriver for the terminal screws.
Gate Status: wired on this board Nimbio PWR+ PWR- Sense 2 SC Sense 1 NC C NO Relay shown de-energized: NO open, NC closed ALL-BLDC circuit board, Rev. 9.0 +24VDC GROUND RELAY-1 COM RELAY-1 N.O. COMMON (row above SAFETY LOOP) EXIT/OPEN CMD 1 → +24VDC PWR+ 2 → GROUND PWR- 6 → EXIT/OPEN CMD NO 5 → COMMON C 4 → RELAY-1 N.O. Sense 1 3 → RELAY-1 COM SC Legend 1. Nimbio PWR+ (red) → +24VDC on the ALL-BLDC circuit board, Rev. 9.0 2. Nimbio PWR- (black) → GROUND on the ALL-BLDC circuit board, Rev. 9.0 3. Nimbio SC (black/white stripe) → RELAY-1 COM on the ALL-BLDC circuit board, Rev. 9.0 4. Nimbio Sense 1 (yellow) → RELAY-1 N.O. on the ALL-BLDC circuit board, Rev. 9.0 5. Nimbio C (grey) → COMMON (row above SAFETY LOOP) on the ALL-BLDC circuit board, Rev. 9.0 6. Nimbio NO (green) → EXIT/OPEN CMD on the ALL-BLDC circuit board, Rev. 9.0 Setting: programmable relay (RELAY-1) = setting 4: ON when gate is not fully closed (gate position indicator) (DIP S1/S2 on the ALL-BLDC board) NC: Not used Sense 2: Not used Cautions RELAY-1 is on newer SL-90 boards only. Older boards have no RELAY-1 (the change appears to date from about 2019), so Gate Status cannot be wired from the operator board on them. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed. Wire colors PWR+ — red PWR- — black Sense 2 — yellow/green stripe SC — black/white stripe Sense 1 — yellow NC — blue C — grey NO — green
Nimbio terminal strip (left) to the ALL-BLDC circuit board, Rev. 9.0 (right). Wire tags name the destination terminal. On a phone, scroll the diagram sideways or pinch to zoom; the Connections list below has every wire.

Connections

Nimbio terminalOperator terminalNumberBoardNote
PWR++24VDC—ALL-BLDC circuit board, Rev. 9.0Rated up to 500 mA for accessories.
PWR-GROUND—ALL-BLDC circuit board, Rev. 9.0
Sense 2Not used——Not used. RELAY-1 is a single N.O./COM contact, and one contact reports one state.
SCRELAY-1 COM—ALL-BLDC circuit board, Rev. 9.0Sense common; the other side of the RELAY-1 contact from Sense 1.
Sense 1RELAY-1 N.O.—ALL-BLDC circuit board, Rev. 9.0RELAY-1 contact; behavior set with DIP S1/S2 (configuration 4).
NCNot used——Not used: the operator input is wired to NO and C.
CCOMMON—ALL-BLDC circuit board, Rev. 9.0The COMMON directly above SAFETY LOOP.
NOEXIT/OPEN CMD—ALL-BLDC circuit board, Rev. 9.0

PWR+

Operator terminal: +24VDCNumber: —Board: ALL-BLDC circuit board, Rev. 9.0Note: Rated up to 500 mA for accessories.

PWR-

Operator terminal: GROUNDNumber: —Board: ALL-BLDC circuit board, Rev. 9.0Note:

Sense 2

Operator terminal: Not usedNumber: —Board: —Note: Not used. RELAY-1 is a single N.O./COM contact, and one contact reports one state.

SC

Operator terminal: RELAY-1 COMNumber: —Board: ALL-BLDC circuit board, Rev. 9.0Note: Sense common; the other side of the RELAY-1 contact from Sense 1.

Sense 1

Operator terminal: RELAY-1 N.O.Number: —Board: ALL-BLDC circuit board, Rev. 9.0Note: RELAY-1 contact; behavior set with DIP S1/S2 (configuration 4).

NC

Operator terminal: Not usedNumber: —Board: —Note: Not used: the operator input is wired to NO and C.

C

Operator terminal: COMMONNumber: —Board: ALL-BLDC circuit board, Rev. 9.0Note: The COMMON directly above SAFETY LOOP.

NO

Operator terminal: EXIT/OPEN CMDNumber: —Board: ALL-BLDC circuit board, Rev. 9.0Note:

When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.

Settings on the operator

The RELAY-1 contact’s behavior is chosen with DIP switches S1 and S2 on the ALL-BLDC board. This guide sets it to configuration 4: active when the gate is not fully closed. Confirm the setting for your site with Nimbio support during installation.

Gate Status

Gate Status: wired. Sense 1 and SC connect across the RELAY-1 contact, set to configuration 4 (DIP S1/S2): active when the gate is not fully closed. Nimbio maps the relay’s two states to the labels shown in the app. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.

RELAY-1 is on newer SL-90 boards only. Older boards have no RELAY-1 (the change appears to date from about 2019), so Gate Status cannot be wired from the operator board on them.

No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.

Frequently asked questions

Does the All-O-Matic SL-90 DC need an expansion board for Gate Status? +

No. Sense 1 and SC land on the RELAY-1 contact of the main ALL-BLDC circuit board.

Which Nimbio terminals open the gate on the All-O-Matic SL-90 DC? +

NO and C, wired to EXIT/OPEN CMD and COMMON. The Nimbio relay closes NO to C, which the SL-90 DC reads as an open command.

Why is Sense 2 not used on the All-O-Matic SL-90 DC? +

RELAY-1 is a single N.O./COM contact. One contact reports one state, so Sense 1 and SC across it is the complete connection; a second sense line on the same contact would only mirror the first.

Is the Nimbio NC terminal used on the All-O-Matic SL-90 DC? +

No. The operator input takes the NO and C pair, so NC stays empty.

Does every All-O-Matic SL-90 DC board have RELAY-1? +

No. RELAY-1 is on newer SL-90 boards only. Older boards have none (the change appears to date from about 2019), so on an older board Gate Status cannot be wired from the operator board.