Wiring guide: DoorKing 6100

This guide shows where each wire from the Nimbio terminal strip lands on the DoorKing 6100’s control board, and which switch setting the relay needs. Gate Status: wired on the main board. Sense 1 and SC connect across the board’s dry relay contact, and Nimbio maps the relay’s two states to the labels shown in the app.

Printable version (PDF)

Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.

Before you start

  • Power the operator down at its supply before touching any terminal.
  • The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires PWR+, PWR-, SC, Sense 1, C and NO; Sense 2 and NC are not used (see “Connections”).
  • Power: PWR+ and PWR- go to a separate power supply, not to the operator board. Terminal 7 (24 VAC) is limited to 250 mA for everything connected to it, so do not power the Nimbio from it. The Nimbio accepts 6.5 to 24 V AC or DC; either supply lead can go to either PWR terminal.
  • You need a small screwdriver for the terminal screws.
Gate Status: wired on this board Nimbio PWR+ PWR- Sense 2 SC Sense 1 NC C NO Relay shown de-energized: NO open, NC closed Separate power supply Supply + (+) Supply – (-) Series 6050/6100 control board Dry Relay Contact (17) Dry Relay Contact (16) Low Voltage Common (20) Full Open (11) 1 → Supply + PWR+ 2 → Supply – PWR- 6 → Full Open NO 5 → Low Voltage Common C 4 → Dry Relay Contact Sense 1 3 → Dry Relay Contact SC Legend 1. Nimbio PWR+ (red) → Supply + (+) on the Separate power supply 2. Nimbio PWR- (black) → Supply – (-) on the Separate power supply 3. Nimbio SC (black/white stripe) → Dry Relay Contact (17) on the Series 6050/6100 control board 4. Nimbio Sense 1 (yellow) → Dry Relay Contact (16) on the Series 6050/6100 control board 5. Nimbio C (grey) → Low Voltage Common (20) on the Series 6050/6100 control board 6. Nimbio NO (green) → Full Open (11) on the Series 6050/6100 control board Setting: Gate Status relay (terminals 16 and 17) = SW4-1 OFF, SW4-2 ON (Not Closed mode) (SW4 on the control board) Setting: Full Open (terminal 11) = SW4-3 ON (standard input), SW4-4 ON (auto-close), SW4-5 ON (swing gate mode) (SW4 on the control board) NC: Not used Sense 2: Not used Cautions Do not power the Nimbio from the operator board. Terminal 7 (24 VAC) is limited to 250 mA for everything connected to it; give the Nimbio its own power supply. The Nimbio accepts 6.5 to 24 V AC or DC, and either supply lead can go to either PWR terminal. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed. Wire colors PWR+ — red PWR- — black Sense 2 — yellow/green stripe SC — black/white stripe Sense 1 — yellow NC — blue C — grey NO — green
Nimbio terminal strip (left) to the Series 6050/6100 control board (right). Wire tags name the destination terminal. On a phone, scroll the diagram sideways or pinch to zoom; the Connections list below has every wire.

Connections

Nimbio terminalOperator terminalNumberBoardNote
PWR+Supply ++Separate power supplyDo not power from the operator board — see “Before you start.”
PWR-Supply ––Separate power supply
Sense 2Not used——Not used. Terminals 16 and 17 are the two sides of one relay contact, and one contact reports one state.
SCDry Relay Contact17Series 6050/6100 control boardSense common; the other side of the dry relay contact from Sense 1.
Sense 1Dry Relay Contact16Series 6050/6100 control boardDry relay contact; behavior set with SW4 switches 1 and 2.
NCNot used——Not used: the operator input is wired to NO and C.
CLow Voltage Common20Series 6050/6100 control board
NOFull Open11Series 6050/6100 control boardAccess-control input.

PWR+

Operator terminal: Supply +Number: +Board: Separate power supplyNote: Do not power from the operator board — see “Before you start.”

PWR-

Operator terminal: Supply –Number: –Board: Separate power supplyNote:

Sense 2

Operator terminal: Not usedNumber: —Board: —Note: Not used. Terminals 16 and 17 are the two sides of one relay contact, and one contact reports one state.

SC

Operator terminal: Dry Relay ContactNumber: 17Board: Series 6050/6100 control boardNote: Sense common; the other side of the dry relay contact from Sense 1.

Sense 1

Operator terminal: Dry Relay ContactNumber: 16Board: Series 6050/6100 control boardNote: Dry relay contact; behavior set with SW4 switches 1 and 2.

NC

Operator terminal: Not usedNumber: —Board: —Note: Not used: the operator input is wired to NO and C.

C

Operator terminal: Low Voltage CommonNumber: 20Board: Series 6050/6100 control boardNote:

NO

Operator terminal: Full OpenNumber: 11Board: Series 6050/6100 control boardNote: Access-control input.

When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.

Settings on the operator

Set these switches on the SW4 switch bank of the control board:

  • Gate Status relay (terminals 16 and 17): SW4-1 OFF, SW4-2 ON (“Not Closed” mode).
  • Full Open (terminal 11): SW4-3 ON (standard input), SW4-4 ON (auto-close), SW4-5 ON (swing gate mode).

Gate Status

Gate Status: wired. Sense 1 (terminal 16) and SC (terminal 17) connect across the dry relay contact. With SW4-1 OFF and SW4-2 ON, the relay is active whenever the gate is not closed, and Nimbio maps its two states to the labels shown in the app. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.

No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.

Frequently asked questions

Does the DoorKing 6100 need an expansion board for Gate Status? +

No. Sense 1 and SC land on the dry relay contact of the main control board, terminals 16 and 17.

Which Nimbio terminals open the gate on the DoorKing 6100? +

NO and C, wired to Full Open (terminal 11) and Low Voltage Common (terminal 20). The Nimbio relay closes NO to C, which the 6100 reads as an open command on its access-control input.

Why is Sense 2 not used on the DoorKing 6100? +

Terminals 16 and 17 are the two sides of one relay contact. One contact reports one state, so Sense 1 and SC across it is the complete connection; a second sense line on the same contact would only mirror the first.

Is the Nimbio NC terminal used on the DoorKing 6100? +

No. The operator input takes the NO and C pair, so NC stays empty.