Knowledge Base › Wiring guide: DoorKing 6100
Wiring guide: DoorKing 6100
This guide shows where each wire from the Nimbio terminal strip lands on the DoorKing 6100’s control board, and which switch setting the relay needs. Gate Status: wired on the main board. Sense 1 and SC connect across the board’s dry relay contact, and Nimbio maps the relay’s two states to the labels shown in the app.
Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.
Before you start
- Power the operator down at its supply before touching any terminal.
- The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires PWR+, PWR-, SC, Sense 1, C and NO; Sense 2 and NC are not used (see “Connections”).
- Power: PWR+ and PWR- go to a separate power supply, not to the operator board. Terminal 7 (24 VAC) is limited to 250 mA for everything connected to it, so do not power the Nimbio from it. The Nimbio accepts 6.5 to 24 V AC or DC; either supply lead can go to either PWR terminal.
- You need a small screwdriver for the terminal screws.
Connections
| Nimbio terminal | Operator terminal | Number | Board | Note |
|---|---|---|---|---|
| PWR+ | Supply + | + | Separate power supply | Do not power from the operator board — see “Before you start.” |
| PWR- | Supply – | – | Separate power supply | |
| Sense 2 | Not used | — | — | Not used. Terminals 16 and 17 are the two sides of one relay contact, and one contact reports one state. |
| SC | Dry Relay Contact | 17 | Series 6050/6100 control board | Sense common; the other side of the dry relay contact from Sense 1. |
| Sense 1 | Dry Relay Contact | 16 | Series 6050/6100 control board | Dry relay contact; behavior set with SW4 switches 1 and 2. |
| NC | Not used | — | — | Not used: the operator input is wired to NO and C. |
| C | Low Voltage Common | 20 | Series 6050/6100 control board | |
| NO | Full Open | 11 | Series 6050/6100 control board | Access-control input. |
PWR+
PWR-
Sense 2
SC
Sense 1
NC
C
NO
When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.
Settings on the operator
Set these switches on the SW4 switch bank of the control board:
- Gate Status relay (terminals 16 and 17): SW4-1 OFF, SW4-2 ON (“Not Closed” mode).
- Full Open (terminal 11): SW4-3 ON (standard input), SW4-4 ON (auto-close), SW4-5 ON (swing gate mode).
Gate Status
Gate Status: wired. Sense 1 (terminal 16) and SC (terminal 17) connect across the dry relay contact. With SW4-1 OFF and SW4-2 ON, the relay is active whenever the gate is not closed, and Nimbio maps its two states to the labels shown in the app. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.
No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.
Frequently asked questions
Need help on site?
Our support team provides live phone assistance during installation.