Knowledge Base › Wiring guide: DoorKing 9070
Wiring guide: DoorKing 9070
This guide shows where each wire from the Nimbio terminal strip lands on the DoorKing 9070’s 4702-010 circuit board, and which switch setting the relay needs. Gate Status: wired on the main board. Sense 1 and SC connect across the board’s dry relay contact, and Nimbio maps the relay’s two states to the labels shown in the app.
Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.
Before you start
- Power the operator down at its supply before touching any terminal.
- The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires PWR+, PWR-, SC, Sense 1, C and NO; Sense 2 and NC are not used (see “Connections”).
- Power: PWR+ and PWR- go to a separate power supply, not to the operator board. Terminal 7 (24 VAC, radio receiver power) is limited to 250 mA for everything connected to it, so do not power the Nimbio from it. The Nimbio accepts 6.5 to 24 V AC or DC; either supply lead can go to either PWR terminal.
- DoorKing revised this control board after 2016 for updated safety standards. The terminal numbers on this page follow the 2009-revision 9050/9070 manual; on a newer board, the labels printed beside the terminals take precedence over the numbers here.
- You need a small screwdriver for the terminal screws.
Connections
| Nimbio terminal | Operator terminal | Number | Board | Note |
|---|---|---|---|---|
| PWR+ | Supply + | + | Separate power supply | Do not power from the operator board — see “Before you start.” |
| PWR- | Supply – | – | Separate power supply | |
| Sense 2 | Not used | — | — | Not used. Terminals 10 and 11 are the two sides of one relay contact, and one contact reports one state. |
| SC | Dry Relay Contact | 11 | 4702-010 circuit board | Sense common; the other side of the dry relay contact from Sense 1. |
| Sense 1 | Dry Relay Contact | 10 | 4702-010 circuit board | Dry relay contact; behavior set with switch 3. |
| NC | Not used | — | — | Not used: the operator input is wired to NO and C. |
| C | Low Voltage Common | 12 | 4702-010 circuit board | |
| NO | Full Open/Close Input | 8 | 4702-010 circuit board | Opens a closed gate; see FAQ for behavior on an open or closing gate. |
PWR+
PWR-
Sense 2
SC
Sense 1
NC
C
NO
When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.
Settings on the operator
The dry relay contact’s behavior is chosen with switch 3 on the 4702-010 circuit board. The manual’s two options are: switch 3 ON, relay active when the gate is in the full open position; switch 3 OFF, relay active when the gate is not closed. Confirm the setting for your site with Nimbio support during installation.
Gate Status
Gate Status: wired. Sense 1 (terminal 10) and SC (terminal 11) connect across the dry relay contact. The relay switches on the gate condition selected with switch 3, and Nimbio maps its two states to the labels shown in the app. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.
No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.