Knowledge Base › Wiring guide: LiftMaster CSL24UL
Wiring guide: LiftMaster CSL24UL
This guide shows where each wire from the Nimbio terminal strip lands on the LiftMaster CSL24UL, and how to set the Expansion Board’s relay switches. Gate Status: requires the LiftMaster Expansion Board. The main board takes the open command; Sense 1, SC and Sense 2 land on the Expansion Board’s AUX RELAY 1.
Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.
Before you start
- Power the operator down at its supply before touching any terminal.
- The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO.
- Power: PWR+ and PWR- go to a separate 12-24 V AC or DC power supply, not to the operator board. The board’s accessory output is rated 500 mA, but Nimbio installations powered from this board have had unstable power.
- Gate Status needs the Expansion Board installed. Without it the Nimbio board can still open the gate.
- You need a small screwdriver for the terminal screws.
Connections
| Nimbio terminal | Operator terminal | Number | Board | Note |
|---|---|---|---|---|
| PWR+ | Supply + | + | Separate power supply | Do not power from the operator board — see “Before you start.” |
| PWR- | Supply – | – | Separate power supply | |
| Sense 2 | NO | — | Expansion Board, AUX RELAY 1 | |
| SC | COM | — | Expansion Board, AUX RELAY 1 | Sense common. |
| Sense 1 | NC | — | Expansion Board, AUX RELAY 1 | |
| NC | Not used | — | — | The EXIT input takes NO and C. |
| C | Com | — | CSL24UL main control board | Lower screw of the EXIT pair (the EXIT input’s own Com). |
| NO | EXIT | — | CSL24UL main control board |
PWR+
PWR-
Sense 2
SC
Sense 1
NC
C
NO
When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.
Settings on the operator
On the Expansion Board, set AUX RELAY 1’s three switches (SW4, SW5, SW6) to OFF, OFF, ON. In the CSL24UL manual’s relay table this selects “Energizes at open limit”.
Gate Status
Gate Status: requires the Expansion Board. With AUX RELAY 1 set to OFF, OFF, ON the relay energizes at the open limit. Sense 2 on NO closes when the gate is fully open, and Sense 1 on NC closes whenever the gate is away from the open limit. Which physical terminal a sense line lands on does not decide whether Gate Status shows Open or Closed — Nimbio sets that per device after installation. If Gate Status ever shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.
No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.
Frequently asked questions
Need help on site?
Our support team provides live phone assistance during installation.
Call 800‑353‑3422 Send a message