Knowledge Base › Wiring guide: LiftMaster CSW200UL and CSW24UL

Wiring guide: LiftMaster CSW200UL and CSW24UL

This guide shows where each wire from the Nimbio terminal strip lands on the LiftMaster CSW200UL and CSW24UL’s main control board, and which expansion-board setting Gate Status needs. Gate Status: needs the expansion board. Sense 2 and SC connect to the expansion board’s AUX RELAY 1, set to report the gate’s open limit, and Nimbio maps the relay’s two states to the labels shown in the app.

Printable version (PDF)

Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.

Before you start

  • Power the operator down at its supply before touching any terminal.
  • The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires Sense 2 and SC; Sense 1 is not used (see “Connections”).
  • Power: PWR+ and PWR- go to a separate 12-24 V AC or DC power supply, not to the operator board. The board’s accessory output is rated 500 mA, but Nimbio installations powered from this board have had unstable power. The Nimbio board draws 40 to 70 mA.
  • You need a small screwdriver for the terminal screws.
Gate Status: needs the expansion board Nimbio PWR+ PWR- Sense 2 SC Sense 1 NC C NO Relay shown de-energized: NO open, NC closed Separate power supply Supply + (+) Supply – (-) CSW200UL main control board EXIT (second screw) EXIT (first screw) Expansion Board N.O. (AUX RELAY 1) COM (AUX RELAY 1) 1 → Supply + PWR+ 2 → Supply – PWR- 6 → EXIT NO 5 → EXIT C 3 → N.O. Sense 2 4 → COM SC Legend 1. Nimbio PWR+ (red) → Supply + (+) on the Separate power supply 2. Nimbio PWR- (black) → Supply – (-) on the Separate power supply 3. Nimbio Sense 2 (yellow/green stripe) → N.O. (AUX RELAY 1) on the Expansion Board 4. Nimbio SC (black/white stripe) → COM (AUX RELAY 1) on the Expansion Board 5. Nimbio C (grey) → EXIT (second screw) on the CSW200UL main control board 6. Nimbio NO (green) → EXIT (first screw) on the CSW200UL main control board Setting: three switches = OFF, OFF, ON (Open Limit Switch) (Expansion Board, AUX RELAY 1 switches 1, 2, 3) NC: Not used Sense 1: Not used Cautions Power Nimbio from a separate 12-24 V AC or DC power supply, not from the operator board. The board’s accessory output is rated 500 mA, but Nimbio installations powered from this board have had unstable power. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed. Wire colors PWR+ — red PWR- — black Sense 2 — yellow/green stripe SC — black/white stripe Sense 1 — yellow NC — blue C — grey NO — green
Nimbio terminal strip (left) to the CSW200UL main control board (right). Wire tags name the destination terminal. On a phone, scroll the diagram sideways or pinch to zoom; the Connections list below has every wire.

Connections

Nimbio terminalOperator terminalNumberBoardNote
PWR+Supply ++Separate power supplyDo not power from the operator board — see “Before you start.”
PWR-Supply ––Separate power supply
Sense 2N.O.—Expansion BoardExpansion-board relay set to report the gate’s open limit.
SCCOM—Expansion BoardSense common; the other side of the relay contact from Sense 2.
Sense 1Not used——Not used. One relay reports one state; Sense 2 and SC are the complete connection.
NCNot used——Not used: the operator input is wired to NO and C.
CEXIT—CSW200UL main control boardShares the Exit pair with NO.
NOEXIT—CSW200UL main control boardSoft open command.

PWR+

Operator terminal: Supply +Number: +Board: Separate power supplyNote: Do not power from the operator board — see “Before you start.”

PWR-

Operator terminal: Supply –Number: –Board: Separate power supplyNote:

Sense 2

Operator terminal: N.O.Number: —Board: Expansion BoardNote: Expansion-board relay set to report the gate’s open limit.

SC

Operator terminal: COMNumber: —Board: Expansion BoardNote: Sense common; the other side of the relay contact from Sense 2.

Sense 1

Operator terminal: Not usedNumber: —Board: —Note: Not used. One relay reports one state; Sense 2 and SC are the complete connection.

NC

Operator terminal: Not usedNumber: —Board: —Note: Not used: the operator input is wired to NO and C.

C

Operator terminal: EXITNumber: —Board: CSW200UL main control boardNote: Shares the Exit pair with NO.

NO

Operator terminal: EXITNumber: —Board: CSW200UL main control boardNote: Soft open command.

When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.

Settings on the operator

The expansion board’s AUX RELAY 1 is set with three switches to Off, Off, On — Open Limit Switch — so it energizes when the gate reaches the open limit. Confirm the setting for your site with Nimbio support during installation.

Gate Status

Gate Status: needs the expansion board. Sense 2 and SC connect to the expansion board’s AUX RELAY 1 (N.O. and COM), set to Open Limit Switch. The relay energizes when the gate reaches the open limit, and Nimbio maps its two states to the labels shown in the app. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.

No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.

Frequently asked questions

Does the LiftMaster CSW200UL and CSW24UL need an expansion board for Gate Status? +

Yes. Sense 2 and SC land on the expansion board’s AUX RELAY 1, not on the main control board.

Which Nimbio terminals open the gate on the LiftMaster CSW200UL and CSW24UL? +

NO and C, wired to the Exit input on the main control board. The Nimbio relay closes NO to C, which the operator reads as a soft open command.

Why is Sense 1 not used on the LiftMaster CSW200UL and CSW24UL? +

AUX RELAY 1 is one relay with one state, set to report the gate’s open limit. Sense 2 and SC across it is the complete connection; a second sense line on the same relay would only mirror the first.

Is the Nimbio NC terminal used on the LiftMaster CSW200UL and CSW24UL? +

No. The operator input takes the NO and C pair, so NC stays empty.

Does this guide apply to both the CSW200UL and the CSW24UL? +

Yes. Both models share this main control board family and terminal layout.

Related articles