Knowledge Base › Wiring guide: LiftMaster SL585UL
Wiring guide: LiftMaster SL585UL
This guide shows where each wire from the Nimbio terminal strip lands on the LiftMaster SL585UL’s main control board, and which expansion-board setting Gate Status needs. Gate Status: needs the expansion board. Sense 2 and SC connect to the expansion board’s AUX RELAY 1, set to report the gate’s open limit, and Nimbio maps the relay’s two states to the labels shown in the app.
Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.
Before you start
- Power the operator down at its supply before touching any terminal.
- The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires Sense 2 and SC; Sense 1 is not used (see “Connections”).
- Power: PWR+ and PWR- go to a separate 12-24 V AC or DC power supply, not to the operator board. The board’s accessory output is rated 500 mA, but Nimbio installations powered from this board have had unstable power. The Nimbio board draws 40 to 70 mA.
- You need a small screwdriver for the terminal screws.
Connections
| Nimbio terminal | Operator terminal | Number | Board | Note |
|---|---|---|---|---|
| PWR+ | Supply + | + | Separate power supply | Do not power from the operator board — see “Before you start.” |
| PWR- | Supply – | – | Separate power supply | |
| Sense 2 | N.O. | — | Expansion Board | Expansion-board relay set to report the gate’s open limit. |
| SC | COM | — | Expansion Board | Sense common; the other side of the relay contact from Sense 2. |
| Sense 1 | Not used | — | — | Not used. One relay reports one state; Sense 2 and SC are the complete connection. |
| NC | Not used | — | — | Not used: the operator input is wired to NO and C. |
| C | EXIT | — | SL585UL main control board | Shares the Exit pair with NO. |
| NO | EXIT | — | SL585UL main control board | Soft open command. |
PWR+
PWR-
Sense 2
SC
Sense 1
NC
C
NO
When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.
Settings on the operator
The expansion board’s AUX RELAY 1 is set with three switches to Off, Off, On — Open Limit Switch — so it energizes when the gate reaches the open limit. Confirm the setting for your site with Nimbio support during installation.
Gate Status
Gate Status: needs the expansion board. Sense 2 and SC connect to the expansion board’s AUX RELAY 1 (N.O. and COM), set to Open Limit Switch. The relay energizes when the gate reaches the open limit, and Nimbio maps its two states to the labels shown in the app. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.
No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.
Frequently asked questions
Need help on site?
Our support team provides live phone assistance during installation.
Call 800‑353‑3422 Send a message