Knowledge Base › Wiring guide: Max Controls 1500
Wiring guide: Max Controls 1500
This guide shows where each wire from the Nimbio terminal strip lands on the Max Controls 1500’s MATRIX 1 control board. Gate Status: wired on the main board. Sense 2, Sense 1 and SC connect to the board’s GATE STATUS block, which reports the gate open and the gate closed as two separate signals.
Note: This operator cannot supply enough continuous power for Nimbio. Use a separate 12–24V AC or DC power supply.
Before you start
- Power the operator down at its supply before touching any terminal.
- The Nimbio terminal strip has eight terminals: PWR+, PWR-, Sense 2, SC, Sense 1, NC, C and NO. This guide wires every terminal except NC (see “Connections”).
- Power: PWR+ and PWR- go to a separate power supply, not to the operator board. The board’s 24V/GND terminals are its own power input, not an accessory output, so do not power the Nimbio from them. The Nimbio accepts 6.5 to 24 V AC or DC; either supply lead can go to either PWR terminal.
- You need a small screwdriver for the terminal screws.
Connections
| Nimbio terminal | Operator terminal | Number | Board | Note |
|---|---|---|---|---|
| PWR+ | Supply + | — | Separate power supply | Do not power from the operator board — see “Before you start.” |
| PWR- | Supply – | — | Separate power supply | |
| Sense 2 | OPEN | — | MATRIX 1 control board | GATE STATUS relay; activates when the gate reaches the open position. |
| SC | COM | — | MATRIX 1 control board | Sense common for the GATE STATUS block’s OPEN and CLOSE relays. |
| Sense 1 | CLOSE | — | MATRIX 1 control board | GATE STATUS relay; activates when the gate reaches the closed position. |
| NC | Not used | — | — | Not used: the operator input is wired to NO and C. |
| C | GND | — | MATRIX 1 control board | Lands on the GND between STRIKE and KEYPAD. |
| NO | STRIKE | — | MATRIX 1 control board |
PWR+
PWR-
Sense 2
SC
Sense 1
NC
C
NO
When the wiring is done, restore power at the supply. A Nimbio support team member then calls to test the gate before you close the panel.
Settings on the operator
No operator setting is changed by this guide.
Gate Status
Gate Status: wired. Sense 2 and Sense 1 connect to the board’s GATE STATUS block (OPEN and CLOSE), and SC connects to the block’s shared COM. The OPEN relay activates when the gate reaches the open position, and the CLOSE relay activates when the gate reaches the closed position, so Gate Status has a separate signal for fully open and for fully closed. Sense-line polarity does not depend on the wiring. Nimbio maps each sense line’s triggered and untriggered state to an Open or Closed label after installation. If Gate Status shows the opposite of the physical gate, contact Nimbio support to have the labels switched; no rewiring is needed.
No suitable output on your operator? A magnetic gate switch can report the gate’s position instead: wire its two leads to Sense 1 and SC for fully closed, or to Sense 2 and SC for fully open. The switch must be a dry contact that puts out no power of its own; if yours puts out power, add a relay that turns it into a dry contact.
Frequently asked questions
Need help on site?
Our support team provides live phone assistance during installation.